Abstract

The literature survey reveals that the studies on evaporation of an alternative refrigerant for R-404A are lacking. In this study, four R-404A alternative refrigerants - two short term refrigerants (R-448A, R-449A) and two long term refrigerants (R-455A, R-454C) - including R-404A were tested in a 7.0 mm O.D. microfin tube. The tests were conducted changing the mass flux from 90 to 300 kg m −2 s −1 , heat flux from 5 to 15 kW m −2 and vapor quality from 0.2 to 0.8. During the test, the saturation temperature was maintained at 10 °C. The heat transfer coefficients of R-404A were higher than those of the alternative refrigerants. However, the difference tended to decrease as the mass flux increased. The higher heat transfer coefficient of R-404A may be due to the smaller temperature glide of R-404A as compared with those of other refrigerants. The microfin / smooth tube heat transfer enhancement ratios of the alternative refrigerants ranged from 1.14 to 1.93. With the mixture correction, pure refrigerant correlations successfully predicted the mixture refrigerant data.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.