Abstract

Power transformers are essential components in electrical power systems as they transform electrical quantities. In practical terms, electrical power systems may experience disturbances such as short-circuit faults, either between phases or to ground. One type of relay used to accommodate these faults is the Over Current Relay (OCR) for phase-to-phase faults and the Ground Fault Relay (GFR) for ground faults. This research evaluates the coordination settings of transformer protection systems at PT PLN (Persero) ULTG Jeneponto by analyzing the characteristics plot of each transformer unit. The evaluation results reveal intersecting characteristics on the high voltage (HV) and medium voltage (MV) sides of Transformers #3 Tallasa and #3 Bulukumba. By implementing recommended settings for these two transformer units, anomalies can be addressed, and the protection system can coordinate effectively.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.