Abstract

This paper presents an experimental and numerical study of the results of a thermal performance test using precast high-strength concrete (PHC) energy piles with W and coil-type ground heat exchangers (GHEs). In-situ thermal performance tests (TPTs) were conducted for four days under an intermittent operation condition (8h on; 16h off) on W and coil-type PHC energy piles installed in a partially saturated weathered granite soil deposit. In addition, three-dimensional finite element analyses were conducted and the results were compared with the four-day experimental results. The heat exchange rates were also predicted for three months using the numerical analysis. The heat exchange rate of the coil-type GHE showed 10–15% higher efficiency compared to the W-type GHE in the energy pile. However, in considering the cost for the installation of the heat exchanger and cement grouting the additional cost of W-type GHE in energy pile was 200–250% cheaper than coil-type GHE under the condition providing equivalent thermal performance. Furthermore, the required lengths of the W, 3U and coil-type GHEs in the energy piles were calculated based on the design process of Kavanaugh and Rafferty. The additional cost for the W and 3U types of GHEs were also 200–250% lower than that of the coil-type GHE. However, the required number of piles was much less with the coil-type GHE as compared to the W and 3U types of GHEs. They are advantageous in terms of the construction period, and further, selecting the coil-type GHE could be a viable option when there is a limitation in the number of piles in consideration of the scale of the building.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call