Abstract

The purpose of this study was to evaluate the effects of various treatment processes as they relate to the development of disinfection by-products (DBPs). At an existing municipal water supply, several tests were performed, including: air-stripping, potassium permanganate (KMnO4) addition, pH adjustment, evaluation of corrosion control inhibitors, final disinfection, and granular activated carbon (GAC) filtration. Several HAAs were shown to increase at higher pH. The use of air stripping greatly reduced the required amount of chlorine disinfectant. Air stripping, permanganate addition, and chloramination reduced DBPs below 20 µg/L. Stiles-Kem 7840 addition effectively controlled lead and copper concentrations in the distribution system. The use of chloramination as a secondary disinfectant is recommended to meet stage 1 of the disinfection by-product rule.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.