Abstract
This paper presents an evaluation method of strength measure for the static voltage stability analysis of the hybrid multi-infeed dc (HMIdc) system, which comprises both the line-commutated converter-based high voltage dc (LCC-HVdc) and voltage source converter-based HVdc (VSC-HVdc) links. For this purpose, the coupled single-port model proposed originally to assess the static voltage stability of ac power systems is first extended in the HMIdc system. In particular, how the LCC-HVdc and VSC-HVdc links should be modeled in the extended coupled single-port model is further investigated. Then, a generalized effective short-circuit ratio (GESCR) index is proposed as a strength measure for the static voltage stability analysis of the HMIdc system using the extended coupled single-port model. The GESCR can resolve the ambiguity encountered by earlier indices arising from empirical reasoning; thus, it is able to indicate the static voltage stability of the HMIdc system more accurately. Finally, the simulated results based on a classical simplified HMIdc system and a modified IEEE 118-bus system, both including two LCC-HVdc links and a VSC-HVdc link, validate the proposed GESCR.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.