Abstract

Multizone airflow network models assume that in a zone air temperature and contaminant concentrations are uniform, and air momentum effects are neglected. These assumptions could cause errors for airflow with strong buoyancy, large contaminant concentration gradient, or strong momentum. This study has found the correlations of the errors and some dimensionless air parameters. The assumption of uniform air temperature is acceptable when the dimensionless temperature gradient is smaller than 0.03. The assumption of uniform contaminant concentration is valid if the corresponding Archimedes number for the source zone is greater than 400. The assumption of neglecting air momentum effect is reasonable when the jet momentum effect is dissipated before reaching an opening in downstream.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.