Abstract

It is commonly assumed in fire modelling that suppression systems can control the heat release rate of a fire. However, many performance-based assumptions are derived from experimental data for sprinklers, and uncertainty remains for their application to water mist systems. In the UK, residential water mist systems are usually tested to the BS 8458:2015 standard, but the heat release rate in these tests is not quantified and focus is instead placed on thermocouple temperatures. This paper details a series of fire tests to the BS 8458:2015 standard for an electronically controlled water mist system. The paper also includes B-RISK zone modelling of these tests to estimate the suppression performance of the system, comparing model outputs to thermocouple test data. Three traditional suppression assumptions, historically derived from experimental data for sprinklers, have been adopted in the zone modelling to examine whether their application following system activation can be extended to the tested water mist system. The work indicates that applying these suppression assumptions remains reasonable in the context of the performance of the tested water mist system, noting the constraints of the test methods in representing a limited number of fire scenarios.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.