Abstract

To study the dynamic thermal response performance of concrete radiant cooling slab, this paper introduces the concept of core temperature layer. Heat transfer process in the concrete slab is divided into three sub-processes, correspondingly, and three heat transfer models are built by reaction coefficient method. Two-dimensional unsteady heat transfer model of concrete cooling slab is established ultimately. Experiments are conducted to test the slab thermal performance in steady and unsteady conditions. Error analysis and consistency verification are presented between the experimental value and calculated results of the model. The relative error between calculation and experimental value is within 2% in steady conditions and within 7% in unsteady conditions. The application scope of the heat transfer model for practical engineering is defined in this paper.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.