Abstract
The authors have proved the feasibility of substitution of a three-phase power-supply system with a single-phase one when calculating three-phase circuits in electric traction network irrespectively of the external power supply arrangement. In addition, calculation features have been established for particular transformer winding connection configurations (Y/Y or Y/Δ). Based on results of an analysis performed for minimizing the methodological error in calculating the short-circuit currents, a single-phase equivalent circuit has been developed for the intersubstation zone of the traction network, which takes into account the connection between two adjacent substations via an overhead transmission line of 110 (220) kV. An example of calculation in accordance with the proposed replacement scheme is given.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.