Abstract

This paper presents a methodology aimed at obtaining the equivalent circuit of regulating transformers. This aspect is insufficiently treated in most current textbooks in which the equivalent circuit of a tapped transformer is not well justified. The document shows how to obtain the equivalent circuit of a regulating transformer with control of voltage magnitude and phase angle, and how to apply it using either physical quantities or per unit (pu) quantities. The resulting equivalent circuit is adequate for steady-state calculations under balanced conditions and neglects transformer core parameters. The usage of per unit values can be made by selecting the base quantities in an arbitrary manner, which is an obvious advantage when the turns ratio must be estimated.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.