Abstract

An insulation resistance reduction case was studied in this paper. An electrical component composed with metal panel, screw and insulation panel occurred flashover after 2-year service. Environment assessment, dust analysis and material analysis were done to find the reduction reason. The result shows that the reduction is caused by conductive dust aggraded on insulation panel surface; the aged surface of insulation material is favor for the conductive dust aggradation; humid air and high-hygroscopic dust accelerate this aggradation. It is suggested to improve the hydrophobicity and anti-aging property of insulation materials as well as increase the creepage for avoiding the kind of failure.