Abstract

During the design stages of a new geothermal heat exchanger special care is devoted to the peak heating and cooling demands of the building. These lead to extreme temperatures in the heat carrying liquid that may cause unwanted material damages in the installation. The short duration of these peak demands, of a few days at most, require the inclusion of the thermal inertia of the heat carrying liquid, the grout, and the ground located close to the boreholes in the theoretical model used to predict the thermal response of the geothermal heat exchanger. By expanding the grout and ground temperatures in terms of conveniently chosen multipoles, the present work develops such a model. The resulting enhanced multipole method, meant originally for peak heating and cooling demands, is also valid in the limit of slowly varying heat injection rates in which it delivers the same results as the classical multipole method developed by Bennet, Claesson, and Hellström.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.