Abstract
The dynamic voltage restorer's (DVR) transient, steady-state, and dynamic responses are essential requirements for protecting sensitive loads against upstream voltage disturbances via the DVR's ride-through capabilities. DVRs also look after transient oscillation at the instant of entering, and /or exiting by the DVR. This paper presents an enhanced, optimized, and less complex DVR control system structure, which is capable of improving the transient, steady-state, and dynamic responses as well as eliminating inherent transient oscillations. The control system comprises a closed-loop feedback control signal and feedforward upstream disturbance detection signal. Incorporating the feedforward term helps, dramatically, in improving the system response and eliminating the transient oscillations in the load voltage. The error signals are adapted using a PI controller to make the load voltage faithfully track its predefined reference waveform. The controller is implemented in the dq synchronous rotating reference frame. The parameters of the PI controller are selected using modern population-based optimization called the Harris Hawks Optimization (HHO) technique. The results obtained using the HHO technique are compared with two other optimization algorithms, namely Particle Swarm Optimization (PSO) and Whale Optimization Algorithm (WOA). The results show that the HHO gives the best system response. The system is simulated using MATLAB/Simulink and the validation via Typhoon HIL402 real-time emulator. Both HIL402 validation and simulation results show that the proposed control scheme recovers normal operation against voltage disturbance within approximately 1.2 milliseconds without overshoot with steady-state error near zero and significantly dampens the inherent voltage oscillation that occurs at the instant of DVR entrance and/or exit.
Highlights
Power quality (PQ) attracted much attention especially in industrial and commercial consumers due to the huge economic losses caused by poor PQ
At t=0.1 sec. to t=0.2 sec., VPCC undergoes a voltage sag of ∼=-30% of its nominal voltage to reach a peak value of 217.7 Volts
For the same time interval, the dynamic voltage restorer (DVR) produces an aiding voltage that counteracts this voltage sag (FIGURE 8.(b)) to result in a load voltage that is almost free of disturbances (FIGURE 8.(c))
Summary
Power quality (PQ) attracted much attention especially in industrial and commercial consumers due to the huge economic losses caused by poor PQ. An integrated higher-order controller was implemented, based on ultra-capacitor (UCAP) DVR to improve the dynamic response of the DVR [15] This technique was successful in voltage-sag compensation within 33 milliseconds. Referring to (2), it can be seen that for good and fast dynamic responses, the voltage drop across the DVR, the voltage disturbance at the load side, as well as the disturbances in the voltage at PCC, are incorporated in the control loop. The section illustrates how the HHO technique is applied to the proposed DVR control system In this stage, HHO remains in certain areas randomly hoping to find the prey based on two tactics. Where, Ym(t) is obtained from equation (15) FIGURE 6 demonstrates a flow chart for the application of the HHO algorithm on the proposed DVR control system
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.