Abstract

The design of air conditioning mechanical ventilation (ACMV) system affects the building energy performance and the indoor pollutant removal process. The present study aims to reduce energy consumption on ACMV systems by employing a renewable air treatment system (ATS). The ATS is able to purify the recirculated air through the ozone-based oxidation process and air scrubbing devices. The air purification performance of primary equipment in the ATS has been studied in order to demonstrate the capability to remove indoor air pollutants. Due to the air purification process, the ATS allows a reduced supply of outdoor-air translating to a lower cooling load. In addition, the reduced outdoor-air fraction results in an improved chiller efficiency. Therefore, the ATS is capable of achieving marked energy savings because of the reduced cooling load for conditioning outdoor airflow. The proposed ATS is particular adept during a period when Singapore faces periodic bad haze situations. Activating the ATS while decreasing the outdoor-air fraction can be an attractive solution. Based on Singapore climatic condition, an energy consumption analysis has been carried out to estimate the energy saving potential of the proposed ATS with varying outdoor-air intake. The “plug-and-play” ATS can be easily integrated into any new or existing ACMV systems to realize immediate improvement in indoor air quality and building energy efficiency.