Abstract

This article presents an experimental analysis of peak load shifting for air conditioning system using PCM (phase change material) in a room. The melting range of the used PCM is from 20 to 25°C. The amount of the PCM is determined according to the cooling load of the room during the peak time. The hourly cooling load is calculated. A low-power fan is used to drive air over the PCM capsules, which are arranged in a chamber above the room. Auxiliary cooling unit is used to freeze the PCM when the night temperature is higher than 18°C. The temperatures of the PCM are measured by 9 thermocouples inserted inside a capsule. The variant degrees of temperature of the air at the inlet, at the middle, and at the outlet of the air-passing chamber as well as at the room are measured during day and night. In addition to that, the climate conditions are measured. As a result, during the peak load shifting time, which is within 2 hours, the decrease of the room temperature is between 7-10 °C by using PCM ceiling system. Consequently, it can be concluded that the PCM system is effective for the peak load shifting.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call