Abstract

Traction networks of alternating current electrified railroads generate large electromagnetic fields with 50 Hz frequency. In points of overhead power lines (OPL) and electrified railroads crossing, traction network electromagnetic fields and overhead power lines interfere with each other, which can result in increase in intensities and appearance of the field complex spatial structure. To determine intensities of electrical and magnetic fields which are created in points of crossing, a procedure for intensities summing has been developed, which is based on fields intensities calculation with Fazonord software application, the fields corresponding to traction network and overhead power line mode. Modeling results indicated that intensities of traction network magnetic field are increased up to 13% by interference of 220 kV intensities power lines magnetic field, while at a regulated height of 1.8 m, magnetic field amplitude equals to 82 A/m. At the same time, OPL can increase traction field electrical field strength in the point of crossing by 66% while reaching 5.5 kV/m at 1.8 m height.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.