Abstract
The increase in the capacity of cleaning and construction vehicles for highcapacity and energy-intensive mines calls for an increase in the supply voltage of cleaning and tunneling combines, as well as transport systems: from a voltage of 660 V switched to 1140 V, and now to 3300 V. This allows improving technical and economic indicators for clearing and access areas, as well as improving the reliability of local Power Supply Systems (PSS). However, this trend prevents the supply of underground electric networks with a voltage of 6 kV, in connection with which the problem arises of increasing the voltage of supply networks. To date, it has become possible to apply the 10 kV voltage to the operation, which is most acceptable for the use of electrical equipment for electrical networks and protection devices. Leading educational, research and design organizations were engaged in research on this issue. An analysis of the results of the research showed that switching to 10 kV voltage is justified and timely. At the same time, 35 kV voltage is not removed from the agenda, which is technically feasible and economically justified, but there are problems with the safety of its operation in underground workings, which requires appropriate refinement. This level of voltage will improve the quality of electricity.Conclusions: 1. Application of 35 kV voltage in the underground power supply system of coal and ore mines is advisable at a depth of more than 1000 m with a maximum load of at least 1000 kVA at the level of the stem cables.2. Application of 35 kV voltage in underground electrical networks will allow to significantly improve the quality indicators of voltage, reliability, and economy of the system due to the current unloading of the most important element of SES, such as stem cables.3. Analysis of the main parameters and characteristics of electrical mine electrical equipment gives reason to believe that it allows implementing a trend of 35 kV deep input to deep horizons of mines (mines) and placement of 35/6 kV substations on working horizons.
Highlights
ЭЛЕКТРОСНАБЖЕНИЕ ПОДЗЕМНЫХ ПОТРЕБИТЕЛЕЙ ГЛУБОКИХ И ЭНЕРГОЕМКИХ ШАХТРост мощностей очистных проходческих и транспортных средств высокопроизводительных и энергоемких шахт вызывает необходимость увеличения напряжения питания очистных и проходческих комбайнов, а также транспортных систем: с напряжения 660 В перешли на 1140 В, а в настоящее время до 3300 В
This trend prevents the supply of underground electric networks with a voltage of 6 kV, in connection with which the problem arises of increasing the voltage of supply networks
1. Application of 35 kV voltage in the underground power supply system of coal and ore mines is advisable at a depth of more than 1000 m with a maximum load of at least 1000 kVA at the level of the stem cables
Summary
Рост мощностей очистных проходческих и транспортных средств высокопроизводительных и энергоемких шахт вызывает необходимость увеличения напряжения питания очистных и проходческих комбайнов, а также транспортных систем: с напряжения 660 В перешли на 1140 В, а в настоящее время до 3300 В. Указанных показателей можно достичь за счет обоснования оптимального класса напряжения подземной системы питания, что позволит в полном объеме и на длительный срок решить вопросы построения эффективных систем электроснабжения глубоких шахт с учетом перспектив развития горных предприятий, связанных с углублением и ростом мощности электрических нагрузок подземных электроприемников. Уменьшение уровня потерь напряжения в линиях обеспечивается увеличением их пропускной способности в процессе проектирования несколькими технически возможными путями, из которых основными являются: 1) замена питающих линий кабелями большего сечения; 2) увеличение количества питающих кабелей; 3) компенсация реактивной мощности (поперечная компенсация) в нерегулируемых приводах с постоянным режимом работы; 4) продольная компенсация реактивных параметров линии; 5) использование более высокого класса напряжения для распределительной сети. В условиях горных предприятий, отдельные потребители которых имеют резкопеременные нагрузки, для относительной стабилизации уровня рабочего напряжения целесообразно использование продольной емкостной компенсации, что обеспечивается последовательным включением к питающей линии батареи конденсаторов.
Published Version (Free)
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have