Abstract
This paper utilizes the Unscented Transform together with Cornish-Fisher expansion to estimate the 2%-value of switching overvoltages when considering the impact of trapped charge and corona attenuation. Simulations were performed using a piecewise linear corona model for twin- and triple-conductor lines. The proposed method was compared to Monte Carlo methods through simulations in PSCAD. The method is shown to be able to estimate the 2%-value with comparable accuracy to methods used in industry today, but with only one fifth of the number of calculations.