Abstract

In this paper the attention is on the heat losses of a main, aboveground supply, hot-water pipeline, whose length is 5430 m. It is situated between the Sostanj Thermal Power Plant (TES) and the Central Energy Station (CES) Velenje as part of the district heating system in the Saleska Valley. It was renovated because major heat losses were identified. A numerical analysis and a comparison between the temperature fields of the pipe’s insulation before and after the renovation was performed to discover the main causes for the high heat losses before renovation. An integral measuring method for determining the heat losses was adapted and used to determine the pipeline’s heat losses after the renovation. Taking into consideration the real operating parameters, the annual energy savings and the consequent operational cost reduction, due to the lower heat losses, resulting from the pipeline renovations, are presented. The calculation is made with measured heat-loss coefficients and is therefore based on the real state of the pipeline. The aim is to show the necessity to investigate the heat losses of a hot-water pipeline whose design or state of insulation is questionable.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.