Abstract

This study investigates the aeroacoustic behaviors of a square truncated perforated diffuser under airflow, commonly used in Air Handling Units (AHUs). The design parameters are fundamentally taken into account to unveil the aeroacoustic performance of the diffuser. Initially, unsteady-state Computational Fluid Dynamics (CFD) simulations are conducted based on models that accurately represent the fluid domain of the chamber with the perforated diffuser in the ANSYS Fluent environment. Subsequently, the Ffowcs Williams and Hawkings (FW-H) method integrated into the software is employed to acquire time-dependent signals from microphones placed in three different locations within a perforated diffuser chamber. Finally, the results are converted to a frequency range of 0-1000 Hz using the Fast Fourier Transform (FFT) method, and the SPL values are obtained. The results show that the microphone location is crucially important to determine SPL and the porosity reduction from 0.55 to 0.35 can reduce SPL by approximately 30-40 dB. Variations in wall thickness of the diffuser fluctuated between 5-10 dB at each frequency value.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.