Abstract

The results of a study performed on crosslinked polyethylene (XLPE) insulated cables tested in the laboratory under accelerated conditions are described. URD-type cables rated at 15 kV were aged at 60 Hz, 6 kV/mm, (150 V/mil) and load cycled daily to 90 degrees C conductor, with water inside the pipe and outside of the samples, for periods of up to 3 years. DC testing was performed before and during the aging. An anticipated significant reduction in the AC breakdown strength is observed in control cables (not DC tested), from 44 kV/mm (1100 V/mil) for unaged cables, to 10 kV/mm (250 V/mil), for aged cables. However, there was no further reduction in the AC breakdown strength of cables subjected to DC testing as compared to those that are not tested with DC. It is concluded that AC breakdown strength is not an effective diagnostic tool for determining the effect of DC testing of URD cables aged under the conditions described.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.