It is noted that the introduction of cables with solid dielectric insulation and of modern splicing technology has imposed new standards and restrictions on cable testing and cable fault locating. The arbitrary use of high voltages and energies during DC, AC, and impulse testing of in-service power cables with solid dielectric insulation frequently programs the cables with defects which become faults after the cables are returned to service. The inadequacy of DC testing in determining the cables' AC breakdown strength, the danger of programming the cables with faults when DC and impulse testing at unnecessarily high voltages, and the advantages of very low frequency (VLF) testing and arc reflection methods (ARM) in locating cable defects and faults are presented. It is concluded that by establishing cable fault locating and cable testing guidelines for cable with solid dielectric insulation, which incorporate current research and available technology, utilities can realize substantial savings in cable replacement, cable rehabilitation, and work force budgets. >

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.