Abstract
In this study, we performed numerical simulations of three-dimensional turbulent flows over an isolated building with a door-type opening by using a CFD model in order to investigate the combined effect of wind and buoyancy on windward single-sided ventilation. Positive and negative temperature differences between the inside and outside of the building were considered. The Archimedes number (Ar) was introduced as an index for evaluating the interaction between buoyancy and wind effects. The interaction between the two opposing forces under a positive temperature difference was found to be destructive, resulting in the combined effect reducing the volume flow rate. Furthermore, the wind effect was found to be dominant for Ar0.5<0.45, with the buoyancy effect beginning to increase at Ar0.5=0.2, and tending to be dominant for Ar0.5>0.45. The two effects were found to be fairly comparable at Ar0.5=0.45. The interaction between the two assisted forces under a negative temperature difference was always constructive, resulting in the combined effect reinforcing the ventilation for all the Archimedes numbers.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Journal of Wind Engineering and Industrial Aerodynamics
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.