Abstract

In this study, we applied a vapor-injection (VI) technique in a cascade heat pump system. The VI was applied to both upper and lower stage cycles. Test results showed that heating and cooling capacities increased by using the VI technique (12% and 6%, respectively); however, the system COP decreased (6.6% at the injection ratio of 16.7%). The cascade system which has a small compression ratio and a cascade condenser, cannot fully utilize the VI's advantages to improve the system COP. However, the VI is effective for the system reliability and capacity improvement. We also found that the VI in the upper and lower stage cycles had different effect on overall cycle operating characteristic.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.