Abstract

Surface flames are far stronger as dust explosion ignition sources than smoldering agglomerates, but surface fire seldom occurs with horizontally deposited non-metallic dust layers. In this paper, the effects of sample orientation on the fire hazard of four non-metallic dust layers were investigated using electric spark ignition. Layer surface inclination angle significantly influenced layer ignition sensitivity and fire hazard. For PMMA dust layers, flame spread velocity (FSV) reached 2.6 mm/s from 0.8 mm/s when the inclination angle was increased from 0° to 50°, while in wood dust layers, sustainable propagating combustion occurred when the inclination angle was increased to 40°. Also, the maximum temperature and FSV of surface fire in wood dust layers were far greater than these of smoldering fires, indicating a greater fire hazard for surface fire. Angle of inclination of combustible powder deposits should be considered when assessing fire and explosion hazard in real process industry situations.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.