Abstract
The jet impingement heat sink integrated with a compact oil-free R-134a vapor compression refrigeration system introduced in a previous work (Oliveira and Barbosa, 2017) is now further evaluated in terms of the influence of the compressor piston stroke, applied thermal load, orifice-to-heater distance (jet length) and ambient (hot end) temperature. The proposed heat sink is a compact active thermal solution for concentrated heat loads because it integrates the evaporator and the expansion device into a single unit, making use of a single two-phase impinging jet as the cooling mechanism. The present analysis is based on the coefficient of performance and other steady-state heat transfer parameters associated with the impinging jet (heat transfer coefficient and heater surface temperature). A reduction of the jet length promoted a more vigorous splattering of the jet on the heated surface, enhancing the droplet breakup, which in turn reduced significantly the critical heat flux. An increase of the hot reservoir temperature increased the jet impingement heat transfer coefficient.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.