Abstract

This paper presents first stage of supersonic flow modelling in gas circuit breakers without an arc. Flow characterisation focused on shock and flow separation phenomenon. Velocity deceleration caused by shock will play a significant role in determining arc cooling performance and will impact thermal interruption capability. Gas properties such as specific heat ratio, density, and viscosity influenced the flow characteristics including shock location, strength and the flow separation process.