Abstract

Line harmonics are usually predetermined under the simplified assumption that the DC current is sufficiently smoothed. But in practical operation of controlled converters, e.g., feeding medium-sized DC drives, DC ripple often cannot be neglected. For the predetermination of line harmonics, this means that the operating point is specified by the EMF and the mean value of the DC current, i.e., the associated control and commutation angles are unknown. The consideration of the basic effects of commutation and DC ripple leads to line current harmonics that are separated into positive and negative sequence systems. Selected results of systematic evaluations show the amplitude and phase as functions of DC reactance as well as of the EMF and mean DC current in the range of usual low- and medium-voltage supply networks. In comparison with the conventional precalculations assuming sufficient DC smoothing, significant deviations occur in the case of higher DC ripple.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.