Abstract

The objective of this paper is to measure the effect of an axial magnetic field (AMF) BAMF and arc current on the anode current density in diffuse vacuum arcs. The experimental geometry included a split anode and a butt-type cathode, both with a diameter of 60 mm. The anode surface was divided into a central area and three symmetrically disposed peripheral annular areas. The central area of the split anode had a diameter of 20 mm. The contact material was CuCr25 (25% Cr). The arc current IARC ranged from 4 to 14 kA (rms) at 50 Hz. The opening velocity was 2.4 m/s. The currents of the four areas on the anode contact were measured using four Rogowski coils situated outside the vacuum chamber. An external uniform AMF BAMF ranging from 0 to 110 mT was applied during the experiment. The observed arc modes were recorded by a high-speed charge-coupled device video camera. The experimental results quantitatively reveal that the current density distribution on the anode surface in the diffuse arc mode was not uniform but concentrated in the central area. The current density in the central anode area at the current peak JPeakArea I decreased with increasing BAMF following a power law. For BAMF of 0–110 mT and IARC of 4–14 kA, JPeakArea I = (2.2 IARC + 0.069 IARC2) BAMF−0.22, where JPeakArea I is in A/mm2, BAMF is in mT, and IARC is in kA. Moreover, the current distribution was uneven in the three peripheral areas.