Abstract

Charge passed of mortars with different aggregate volume fractions was tested according to ASTM C1202, and the differential expression of the Ohm law was introduced to explain the relationship between charge passed data and aggregate fractions.Cl- penetration depth of the corresponding mortars and concretes was measured to illustrate the influence of the aggregate volume fraction on their chloride permeability. It was shown that the charge passed of mortar was negatively correlated with aggregate volume fractions, and high aggregate fraction bearing concrete with low charge passed did not necessarily mean low permeability. As a result, the influence of aggregate fraction on charge passed should be taken into consideration when charge passed data was employed to evaluate Cl- permeability of concrete.