Abstract

A water-cooled chiller system in an air-conditioned hotel can take up about one-quarter of the total electricity consumption and considerable amounts of water in the heat rejection process. This paper evaluates operating cost savings of a chiller system integrated with optimal control of cooling towers and condenser water pumps. A sophisticated chiller system model was used to ascertain how different control methods influence the annual electricity and water consumption of chillers operating for the cooling load profile of a reference hotel. It is estimated that applying load-based speed control to the cooling tower fans and condenser water pumps could reduce the annual system electricity use by 8.6% and operating cost by 9.9% relative to the equivalent system using constant speed fans and pumps with a fixed set point of 29.4 °C for cooling water temperature control. The ways to implement this advanced control for system optimization are discussed.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.