Abstract
AbstractDynamic suboptimal control of a heat pump/heat storage system, recovering heat from a ground source and supplying it to a building via a storage tank, is investigated when the utilities offer time‐of‐day energy price incentives. On the basis of the analytical solution to the periodic optimization problem,1 suboptimal trajectories for the general time‐varying case are developed and a method for dealing with transition trajectories from one day to the next is given. The transition trajectories are very close to the numerically generated optimal trajectories and are simple enough to be implemented on microprocessors by use of standard PI controllers.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.