Abstract

To study the dynamic charge characteristics of XLPE cables. In this paper, a Qt test system is built in the laboratory to test the Qt dynamic charge characteristics of different thermal aging samples, and the current characteristics of different aging degrees are obtained according to the charge test differentiation. The experimental results show that the charge value of unaged sample is about 1100 nC, and the charge value of aged sample is about 2000 nC. At the moment of pressurization, the XLPE cable sheet sample flows through a large instantaneous charging current, and the initial current is more than 10−9 orders of magnitude. For the unaged sample, the charge accumulation value and conduction current value of H1 and H2 are better than those of F sample. The analysis shows that due to the insufficient aging degree of the sample, the initial aging stage is in the recrystallizaon stage.