Abstract

A procedure for deriving a dynamic model of an air condition system was described in this paper. The system consisted of a zone, cooling coils and fan. Room thermal balance model and dynamic model of AC control system components including sensor, cooling coils and ducts, were established. This model accurately predicts the effect of inlet air temperature during closed loop control of output air temperature using chilled water flow rate as a control input. Fuzzy adaptive control (FAC) combined with proportional integral derivative (PID) control algorithms (FAC-PID) were used to control the chilled water flow rate. Computational simulations were carried out in toolbox Simulink of Matlab. The fuzzy parameters were carefully tuned to produce less oscillatory responses. The results show that the system based on FAC-PID control is capable of controlling the disturbance efficiently with less time lag and small error than PID control.