Abstract

This paper deals with dynamic behavior of a 21-level (line-to-line) BTB system based on series connection of sixteen converter-cells under a single-line-to-ground (SLG) fault condition. When the SLG fault happens, an imbalance in the supply voltage brings an amount of negative-sequence current to the BTB system. The negative-sequence current should be mitigated because it would result in an increased supply current and a dc-capacitor voltage fluctuation. This paper proposes a new control method intended for reducing both negative-sequence current and dc-voltage fluctuation to acceptable levels. A laboratory system rated at 200 V and 20 kW confirms the validity of the control method. In addition, this paper addresses the issue of magnetic saturation in the 16 three-phase transformers.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.