Abstract

In the event of a single line to ground (SLG) fault in a non-effectively grounded distribution network, the faulted current is weak (only a few amperes or less) and the existing devices cannot accurately judge the faulted feeder. In this paper, we proposed algorithms that combine CEEMDAN (Complete ensemble empirical mode decomposition with adaptive noise) and Hilbert-transform to construct a multi-criteria comprehensive voting method. First, CEEMDAN algorithm is used to decompose the zero-sequence current to obtain the IMF1 (the first intrinsic mode function) component and the Hilbert transform is used to calculate the instantaneous amplitude and instantaneous phase. Then, according to the three largest instantaneous amplitudes information, we constructed the CIP (Characteristic instantaneous phase), CIE (Characteristic instantaneous energy) relative entropy and CICP (Characteristic instantaneous zero sequence current polarity) criteria from the phase, energy and polarity, respectively. Last, we proposed a comprehensive voting method, which is specifically shown as follows: when two or more criteria show that one feeder or the bus has a SLG fault, it is voted that the feeder or the bus has a SLG fault. In contrast, if the judgment results of the three criteria are inconsistent, then we would return to recalculation and then vote. Compared with existing method, simulation tests and field experiments show that the method proposed in this paper has higher accuracy and a faster calculation speed.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call