Abstract

AbstractAn established body of research over many decades has identified the importance of both bulk‐water and pipe scale surface microenvironment buffering to meet distribution system pH targets and reduce corrosivity toward metallic piping and components. Buffer intensity quantifies the ability of water to resist pH changes, and the greater the buffer intensity, the more resistant the water is to pH changes. To provide a practical tool for exploring buffer intensity, a buffer intensity simulator (BIS) was implemented in open‐source R code, incorporating typical chemical species (e.g., carbonate and orthophosphate) that contribute to drinking water buffer intensity along with temperature and ionic strength impacts. The BIS was verified against a parallel spreadsheet implementation and is publicly available at https://github.com/USEPA/BIS. Simulations were conducted to illustrate impacts related to buffer intensity using three practical scenarios: carbonate buffering in drinking waters, temperature impacts, and free ammonia presence from chloramine use and/or source water presence.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.