Abstract

In this paper, a careful analysis of directional element behavior applied to a half-wavelength transmission line (HWL) is presented. Single line-to-ground (SLG) faults were applied, varying loading conditions and fault resistance. A commercial relay was used. Two directional elements were considered: 32QG and 32V. With the aim of obtaining directional element setting parameters, a Python program based on two-port network theory was developed. The simulations were also performed in a hardware-in-the-loop (HIL) environment. It was observed that only the element 32V operated properly throughout the system during SLG fault conditions. It can be concluded that the conventional directional element algorithm can be applied to a system with a half-wavelength transmission line under the above-mentioned fault condition.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.