Abstract
In addition to periodic components of industrial frequency, the aperiodic ones arise in windings and on the generator output leads under the conditions of shortcuts. These aperiodic components slow down the operation of the main differential protection of a generator up to ten periods of a network frequency with the application of saturated magnetic cores of current transformers as well as zero current relays and transformer differential protection [1]. This slowing down promotes accidents and can even lead to generator’s winding and steel burn-out at high-ampere currents. The present paper considers the ways to reduce the impact of aperiodic components on the operation of digital relay protection of generators and generator-transformer blocks and proposes generator’s directional digital protection.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IOP Conference Series: Materials Science and Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.