Abstract
Unbalance and reactive power currents of electric railway will result in poor power quality of three-phase industrial power grid. A co-phase traction power supply system is introduced in this paper to solve these problems by adopting single-phase ac-dc-ac converter. The converter is connected between two secondary windings of traction transformer with abilities of active power transmission and reactive power compensation. Because of the power conversion, the co-phase supply system can utilize single-phase feeding connection scheme instead of traditional two-phase feeding scheme. An actual 10 MVA/27.5 kV co-phase system with impedance-matching balance transformer is designed, developed, and tested. Its real-time detection, control, and distribution algorithms with field programmable gate array-based implementation are introduced. Some test running results validate the performance of the digital controller and demonstrate the feasibility of the proposed co-phase power supply system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.