Abstract
Burnt clay bricks are widely used as a construction material in Pakistan, and their testing for quality confirmation is frequently needed for new and old bricks used in existing structures. The destructive testing methods are time-consuming and not always feasible for testing the bricks used in existing structures. The current study investigated the feasibility of using the ultrasonic pulse velocity (UPV) test as a non-destructive technique to assess the quality of both new and old bricks in masonry structures. A relationship was developed after performing the UPV test followed by a compression test on burnt clay brick samples of five different ages acquired from different sources. The acquired brick samples ranged from new to a century old. Consequently, as a novel contribution, brick quality assessment criteria based on UPV were proposed according to which a UPV value greater than 3000 m/s represents an excellent first-class brick whereas a UPV value lower than 2000 m/s shows a second-class brick. Further, the effectiveness of the UPV test to assess the compressive strength of old bricks was demonstrated with a case study of a 100-year-old masonry structure. The research concluded with the remarks that the compressive strength of bricks can be assessed with reasonable accuracy using the UPV test. The developed quality assessment criteria can be used to quickly check the quality of new and old burnt clay bricks.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.