Abstract

500-kV XLPE-insulated cable with an insulation thickness of 27 mm has been developed for long-distance transmission lines. Basic studies on 500-kV XLPE cable have shown that contaminants in the insulation may be the factor determining electrical performance. This hypothesis is justified by the good correlation obtained between statistical estimations of the size of the largest contaminant in the insulation and the electrical characteristics of full-sized cables. Voltage-withstand and long-term tests have confirmed the design values for minimum breakdown stress, for AC and impulse voltage, and for the degradation coefficients.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.