Abstract

This paper presents the results of fire test of an I-beam protected by a combined magnesite plate-magnesite mixture heat-insulating material. It was shown that a composite with an average thickness of 37 mm maintained an average temperature of 380 °C on the metal surface after 150 minutes of fire exposure, not exceeding the critical value of 500 °C. From 60 to 100 minutes of fire testing (furnace temperature of 980-1025 °C), the temperature of the metal did not exceed 100 °C. This was achieved both due to the high thermal insulation properties of the magnesite mixture, and due to gas and vapor release from the hydration products of magnesia cement. The developed fire-retardant material provides the first group of fire-retardant efficiency (150 minutes) and, after the fire test, is characterized by density of 352.4 kg/m3 and compressive strength of 0.85 MPa, which is three times lower than the original.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.