Abstract

In this paper, the causes analysis of the cracking accident at the lead clamp weld-fusion line of transformer in the extra-high voltage substation was conducted.On-site non-destructive detection of weld defects was carried out to determine the size and location of the defects. An anatomical analysis of the clamp sample revealed that there was serious incomplete penetration and incomplete fusion in the internal structure of the weld, which seriously affected the structural strength of the weld. The causes of welding defects were further analyzed, and suggestions for improving product quality and strengthening inspection supervision were put forward.