Abstract

In this paper, the design procedure of a 14.4 kV output voltage, 100 kHz transformer with an isolation voltage of 115 kV using Litz wire is presented. All design models, including a generalized magnetic model for the leakage and the loss calculations as well as an electrical model for the parasitic capacitance estimation for the transformer are derived and proven by measurements. For designing the insulation, a comprehensive design method based on an analytical maximum electrical field evaluation and an electrical field conform design is used. The resulting design is verified by long and short term partial discharge measurements on a prototype transformer.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.