Abstract

A procedure is presented which enables one to design a current transformer (CT) to meet arbitrary specifications on the required number of cycles of accurate secondary current following a system short circuit which results in a fully offset short circuit current waveform. The procedure enables one to relate the resulting current transformer design to its physical characteristics and to its accuracy classification. The procedure also enables one to account for an arbitrary amount of remanent flux in the current transformer resulting from previous short circuit currents.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.