Abstract

Centrifugal compressors are major components in LNG liquefaction plants. Design considerations for optimal selection and proper sizing of compressor drivers include large starting torque requirements to enable compressor start from settle-out conditions and to prevent flaring the gas. Start-up capabilities of the motor driver can significantly impact the reliability and operability of the compressor train. API 617 on centrifugal compressors refers to API 546 for synchronous motor drivers. In this paper, requirements of API 617 and 546 are reviewed and several important design and sizing requirements are presented. In the effort to optimize plant design, and maintain the performance requirements, the paper discusses optimization options, such as direct on line starting method to explore the motor rating limits, and the use of synchronous motors for power factor correction to eliminate or reduce the need for reactive power compensation by capacitor banks. This paper presents a novel approach to show constant reactive power lines on traditional V curves. It also complements capability curves of synchronous motors with lines of constant efficiency.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.