Abstract

This objective of this project is to determine the energy and environmental potential of distributed common loop water source heat pump system in a near or net-zero commercial office building, which has simultaneous heating and cooling load in winter and shoulder seasons. It is expected that the perimeter zones will have heating demand during those months, while the core zones will have consistent cooling demand throughout the year. The motive is to reclaim the rejected heat from the cooling operation and transfer it to the zones requiring heating. The building under study is a 60,000 ft2 three storey commercial office building, which has private offices along the perimeter, and open work area in the core. In the first part of the analysis, the base building has been modelled and simulated to the minimum requirements of ASHRAE 90.1-Energy Standard for Buildings except Low-Rise Residential Buildings using simulation software eQuest 3.65. The Heating Ventilation and Airconditioning (HVAC) system used is four-pipe fan coil system serving individual zones. The fan coil units use a centralized natural gas boiler and a variable capacity centrifugal chiller as external source of heating and cooling respectively. The base case consumes a total of 524.54 x 1000 kWh of electricity and 1,056 million Btu of natural gas annually. The second part is the modelling and simulation of a proposed case, which uses the same building envelope, occupancy, lighting and equipment as the base case. The HVAC system used is a distributed common loop heat pump system connected to a cooling tower for heat rejection, and a condensing boiler for heat addition. During the occupied hours, when simultaneous cooling and heating loads exist in the building, the cooling zone heat pumps rejects exhaust heat into the common loop, and the heat is subsequently used by the heat pumps operating in heating mode. Using this method, the heat pump system reduces its dependence on the cooling tower and the boiler, which only operate to maintain the loop temperature in an acceptable range. There is 9,510 kWh (1.81%) increase in electricity consumption by proposed case comparing to the base building. Natural gas consumption has been reduced by 353.65 million Btu (33.48%). Annual utility bill has increased by $1,483.00 which is 1.88% higher than the base case. 15.7 tonnes of greenhouse gas can be reduced if the proposed case is adopted.

Highlights

  • The purpose of this project is to examine energy saving potential of an office building located in Toronto by modelling it to ASHRAE 90.1 standard and using distributed water loop heat pump (DWLHP) system for providing simultaneous heating and cooling in different zones

  • By gather data from a heat pump manufacturer, it was found that the cooling energy efficiency ratio (EER) increases from 11 to 20 when the loop supply temperature decreases from 85 °F to 50 °F, and the heating Efficiency Ratio (EER) increases from 17 to 19.5 when the supply temperature increases from 50 °F to 85 °F

  • From the energy and environmental consideration, the common loop water source heat pump system is a significantly better option than the base case; from the economic point of view, the base case is better than the proposed case

Read more

Summary

Purpose of the Project

The purpose of this project is to examine energy saving potential of an office building located in Toronto by modelling it to ASHRAE 90.1 standard and using distributed water loop heat pump (DWLHP) system for providing simultaneous heating and cooling in different zones. Often the office buildings have cooling load in the core zones during the winter season because of heat generated from occupancy, lighting and other office equipment. Buildings lose heat to the ambient during the winter because of the difference between the indoor design temperature and the outdoor temperature. During the unoccupied hours of winter, interior heat generation does not take place. To eliminate the role of external heat generating equipment, the cumulative daily heat rejection to the common water loop must exceed the cumulative daily heat extracted

Energy Use of Commercial
Commercial Building heating and cooling load characteristics
Building Heating Ventilation and Air-Conditioning (HVAC) System
Heat Pump Technology
Energy Efficiency Requirement for Internal Closed Loop Heat Pumps (NRCan, 2016)
HVAC Zoning in eQuest (Hirsch & Associates, 2009)
1.10 Net Zero Energy Building (Duncan, 2009) A Net Zero Energy
Simulation Overview (Clarke, 2001) In the book “Energy Simulation in
Building Envelop Design for Energy Balance (Chwieduk, 2014)
Net Zero Energy Building Design
Design of Typical Water Source Heat Pump Systems
Daikin McQuay Inc Design Guide
Thermal Performance of Water Source Heat Pumps
Thermodynamic Performance Analysis of Water Source Heat Pump in Various Operating Condition
Energy Conservation Using Closed Loop Heat Pump in Commercial Office Building
Optimizing Water Loop
Office building-Heat recovery using water source heat pumps
Objective and Methodology
The Base Case
Proposed Case 1
Result Comparison
Greenhouse Gas Emission
Proposed Case 3
Proposed Case 4
Comparison between the base case and proposed case 3
Findings
Conclusion
Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.