Abstract
The aim of the secondary voltage control is to maintain voltage magnitudes of several load buses, which have been selected as pilot buses, at their optimal values imposed by the tertiary voltage control. In this paper a comprehensive formulation of the secondary voltage control is presented. Centralized control matrices for an optimal proportional integral control are obtained by the minimization of a performance index. Conditions to achieve a stable closed-loop in a decentralized control scheme are stated. A systematic methodology for selecting pilot buses and for dividing the system in decentralized control areas is presented. The differences between centralized and decentralized control schemes are analyzed in a case study based on the New England 39 bus system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.