Abstract

Abstract In this paper, a decentralized nonlinear coordinated excitation and steam valve adaptive control combined with a modified high-order sliding mode differentiator is designed for multi-machine power system stability enhancement. The proposed control scheme is based on Lyapunov’s direct method and requires only local information on the physically available measurements of relative angular speed, active electric power and terminal voltage with the assumption that the power angle and mechanical power input are not available for measurement. Each synchronous generator is considered as a classical fifth order model that includes turbine dynamics. The simplicity of the proposed scheme and its robustness with respect to large perturbations, change in operating point and parameter uncertainties constitute the main positive features. Simulation results in the case of the Kundur 4-machines 2-area power system show the effectiveness, robustness and superiority of the proposed scheme over the classical AVR/PSS.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.